SSI700 User Manual Description of Function Codes
www.ssinverter.info
Property
Default
Setting
Range
Parameter
Name
Function
Code
Group 10: Process Control PID Function
☆
0
0: AI1
1: AI2
2: Reserved
3: AI1 – AI2
4: Pulse setting (DI5)
5: Communication setting
6: AI1 + AI2
7: MAX (|AI1|, |AI2|)
8: MIN (|AI1|, |AI2|)
PID feedback source
10-02
This parameter is used to select the feedback signal channel of process PID.
The PID feedback is a relative value and ranges from 0.0% to 100.0%.
Property
Default
Setting
Range
Parameter
Name
Function
Code
Group 10: Process Control PID Function
☆
0
0: Forward action
1: Reverse action
PID action direction
10-03
•
0: Forward action
When the feedback value is smaller than the PID setting, the AC drive's output frequency
rises. For example, the winding tension control requires forward PID action.
•
1: Reverse action
When the feedback value is smaller than the PID setting, the AC drive's output frequency
reduces. For example, the unwinding tension control requires reverse PID action.
Notes
that this function is influenced by the DI function 35 "Reverse PID action direction".
Property
Default
Setting
Range
Parameter
Name
Function
Code
☆
1000
0–65535
PID setting feedback
range
10-04
This parameter is a non-dimensional unit. It is used for PID setting display (D0-15) and
PID feedback display (D0-16).
Relative value 100% of PID setting feedback corresponds to the value of 10-04. If 10-04 is
set to 2000 and PID setting is 100.0%, the PID setting display (D0-15) is 2000.
Property
Default
Setting
Range
Parameter
Name
Function
Code
☆
20.0
0.0–100.0
Proportional gain Kp1
10-05
☆
2.00s
0.01–10.00s
Integral time Ti1
10-06
☆
0.000s
0.00–10.000
Differential time Td1
10-07
•
10-05 (Proportional gain Kp1)
It decides the regulating intensity of the PID regulator. The higher the Kp1 is, the larger
the regulating intensity is. The value 100.0 indicates when the deviation between PID
feedback and PID setting is 100.0%, the adjustment amplitude of the PID regulator on the
output frequency reference is the maximum frequency.
•
10-06 (Integral time Ti1)
It decides the integral regulating intensity. The shorter the integral time is, the larger the
regulating intensity is. When the deviation between PID feedback and PID setting is
100.0%, the integral regulator performs continuous adjustment for the time set in 10-06.
Then the adjustment amplitude reaches the maximum frequency.
Summary of Contents for SSI700
Page 1: ......
Page 3: ...Safety Information and Precautions...
Page 7: ...Product Information...
Page 12: ...Mechanical and Electrical Installation...
Page 19: ...Operation Display and Application Examples...
Page 42: ...Function Code Table...
Page 64: ...Description of Function Codes...
Page 131: ...EMC...
Page 137: ...Selection and Dimensions...
Page 141: ...Maintenance and Troubleshooting...