Operation
9.2 Parameterizing using the BOP20 (Basic Operator Panel 20)
SINAMICS DCM DC Converter
368
Operating Instructions, 12/2018, A5E34763375A
9.1.5.5
Information on BICO technology
Binector-connector converters and connector-binector converters
Binector-connector converter
●
Several digital signals are converted to a 32-bit integer double word or to a 16-bit integer
word.
●
p2080[0...15] BI: PROFIdrive PZD send bit-serial
Connector-binector converter
●
A 32-bit integer double word or a 16-bit integer word is converted to individual digital
signals.
●
p2099[0...1] CI: PROFIdrive PZD selection receive bit-by-bit
Fixed values for interconnection using BICO technology
The following connector outputs are available for interconnecting any fixed value settings:
●
p2900[0...n] CO: Fixed value_%_1
●
p2901[0...n] CO: Fixed value_%_2
●
p2930[0...n] CO: Fixed value_M_1
Example:
These parameters can be used to interconnect the scaling factor for the main setpoint or to
interconnect an additional torque.
9.2
Parameterizing using the BOP20 (Basic Operator Panel 20)
9.2.1
General information about the BOP20
The BOP20 can be used to power drives up and down during the commissioning phase as
well as display and modify parameters. Faults can be diagnosed as well as acknowledged.