Connecting
6.9 Assignment of terminals and connectors
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
171
Devices
Data
2200 A - 3000 A
1U1, 1V1, 1W1: 10 x 120 mm copper busbar, through hole for M12
1C1, 1D1: Copper busbar, cross-section 60 x 10 mm / 323 mm wide, insert nut M12
Max. conductor cross-section for cables with cable lug according to DIN 46234:
1U1, 1V1, 1W1: 6×240 mm
2
1C1, 1D1: 8×240 mm
2
Tightening torque for 1U1, 1V1, 1W1, 1C1, 1D1: 44 Nm
Tightening torque for protective conductor: 60 Nm
See Chapter "Dimension drawings (Page 80)" for how the protective conductor can be connected.
Note:
If the device is stored for a longer period of time, a layer of corrosion can form on the bare metal surfaces of the housing.
Before connecting the protective conductor, this must be removed from the connection points.
The devices are designed for a permanent line supply connection in accordance with
EN 61800-5-1.
The conductor cross-sections (also for the protective conductor) must be determined in
accordance with the applicable regulations that apply in each case – e.g. EN 60204-1.
Table 6- 25 Assignment of power connections
Terminal
Function
Technical specifications
1U1
1V1
1W1
Power unit line connection,
armature circuit
See Chapter "Technical data (Page 39)"
Protective conductor PE
1C1 (1D1)
1D1 (1C1)
Motor connection, armature
circuit