Operation
9.2 Parameterizing using the BOP20 (Basic Operator Panel 20)
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
371
BOP20 functions
Table 9- 7
Functions
Name
Description
Backlighting
The backlighting can be set using p0007 in such a way that it switches itself off automatically
after the set time if no actions are carried out.
Switch active drive
From the BOP perspective, the active drive is defined using p0008 or using the keys "FN" and
"Arrow up".
Units
The units are not displayed on the BOP.
Access level
The access level for the BOP is defined using p0003.
The higher the access level, the more parameters can be selected using the BOP.
Parameter filter
Using the parameter filter in p0004, the available parameters can be filtered according to their
particular function.
Select status display
Actual values and setpoints are displayed on the status display.
The status display can be set via p0006.
User parameter list
Parameters can be selected for access using the user parameter list in p0013.
Hot swapping
The BOP can be unplugged and plugged while energized.
•
The ON and OFF keys have a function.
When unplugging, the drives are stopped.
After plugging, the drives must be switched on again.
•
The ON and OFF keys have no function
Unplugging and plugging has no effect on the drives.
Key operation
The following applies to the "P" and "FN" keys:
•
When used in a combination with another key, "P" or "FN" must be pressed before the
other key.