Descriptions of functions
10.4 Communication via PROFIBUS DP
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
455
10.4
Communication via PROFIBUS DP
10.4.1
PROFIBUS connection
WARNING
Electric shock during connection while voltage is present
When connecting the PROFIBUS cable while voltage is present, there is a danger of
coming into contact with live components behind the terminal.
Touching live components can result in death or serious injury.
•
Only connect the PROFIBUS cable to connector X126 when the unit is in a de-
energized state.
Position of PROFIBUS connection and diagnostics LEDs
The PROFIBUS connection and diagnostics LEDs are located on the Control Unit (CUD).
The PROFIBUS connection is via a 9-pin Sub-D socket X126. The connections are
electrically isolated.
See also Figure 6-44 Terminal/connector arrangement on the "Control Unit (CUD)"
(Page 156) and Chapter "Description of the LEDs on the CUD (Page 635)".
PROFIBUS connection
Table 10- 33 PROFIBUS connector assignment
Connector
X126
Pin
Signal name
Technical specifications
1
-
Not assigned
2
-
Not assigned
3
RxD/TxD-P
RS485 receive/transmit data P (B)
4
CNTR-P
Control signal (TTL)
5
DGND
PROFIBUS data ground
6
VP
Positive supply voltage (5 V +/-10%)
7
-
Not assigned
8
RxD/TxD-N
RS485 receive/transmit data N (A)
9
-
Not assigned
"Control Unit (CUD)" module