Descriptions of functions
10.34 Diagnostics
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
649
Note
The individual faults and alarms are described in the section titled "Faults and alarms" in the
SINAMICS DCM List Manual. Here you can also find a section titled "Function diagrams"
→
"Faults and alarms", which contains function diagrams for the fault buffer, alarm buffer, fault
trigger, and fault configuration.
Properties of faults and alarms
●
Faults
–
Are identified by Fxxxxx
–
Can lead to a fault reaction
–
Must be acknowledged once the cause has been remedied
–
Status via Control Unit and LED RDY
–
Status via PROFIdrive status signal ZSW1.3 (fault active).
–
Entry in the fault buffer
●
Alarms
–
Are identified by Axxxxx
–
Have no further effect on the drive unit
–
The alarms are automatically reset once the cause has been remedied. No
acknowledgment is required.
–
Status via PROFIdrive status signal ZSW1.7 (alarm active).
–
Entry in the alarm buffer
●
General properties of faults and alarms
–
Can be configured (e.g. change fault to alarm, fault reaction)
–
Triggering on selected messages possible
–
Initiation of messages possible via an external signal
–
Contains the component number for identifying the SINAMICS component involved
–
Contains diagnostic information on the message involved