Additional system components
7.3 Sensor Module Cabinet-Mounted SMC30
SINAMICS DCM DC Converter
212
Operating Instructions, 12/2018, A5E34763375A
7.3.3.5
X521/X531 alternative encoder system interface
Table 7- 16 X521/X531 alternative encoder system interface
Connector Terminal
Designation
Technical specifications
X521
X531
1
A
Incremental signal A
2
A*
Inverse incremental signal A
3
B
Incremental signal B
4
B*
Inverse incremental signal B
5
R
Reference signal R
6
R*
Inverse reference signal R
7
CTRL
Control signal
8
M
Ground
1
P_encoder 5 V/24 V
Encoder supply
2
M_Encoder
Ground, encoder supply
3
- Temp
Temperature sensor KTY84-1C130
4
+ Temp
Temperature sensor KTY84-1C130
5
Clock
SSI clock
6
Clock*
Inverse SSI clock
7
Data
SSI data
8
Data*
Inverse SSI data
Max. connectable cross-section: 1.5 mm
2
Measuring current via the temperature sensor connection: 2 mA
When unipolar HTL encoders are used, A*, B*, and R* on the terminal block must be jumpered with
M_Encoder (X531)
1)
.
1)
Because the physical transmission properties are more robust, the bipolar connection should
always be used. The unipolar connection should only be used if the encoder type does not output
push-pull signals.
WARNING
Electric shock due to unconnected cable shields
Hazardous touch voltages can occur through capacitive cross-coupling due to unconnected
cable shields.
•
Attach the cable shield to the component via terminals for the encoder system
connection.