Descriptions of functions
10.3 Communication according to PROFIdrive
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
439
Properties of the cyclic interfaces IF1 and IF2
The following table shows the different features of the two cyclic interfaces:
Table 10- 26 Properties of the cyclic interfaces IF1 and IF2
Feature
IF1
IF2
Setpoint (BICO signal source)
r2050, r2060
r8850, r8860
Actual value (BICO signal sink)
p2051, p2061
p8851, p8861
PROFIdrive conformance
Yes
No
PROFIdrive telegram selection (p0922)
Yes
No
Isochronous mode possible (p8815[0])
No
No
PROFIsafe possible (p8815[1])
No
No
Direct data exchange (PROFIBUS only)
Yes
Yes
List of drive objects (p0978)
Yes
Yes
Max. PZD (16-bit) setpoint / actual value DC_CTRL 64 / 64
64 / 64
Max. PZD (16-bit) setpoint / actual value encoder
4 / 12
4 / 12
Max. PZD (16-bit) setpoint / actual value TM31
5 / 5
5 / 5
Max. PZD (16-bit) setpoint / actual value
TM15DI_DO
5 / 5
5 / 5
Max. PZD (16-bit) setpoint / actual value TM150
5 / 5
5 / 5
Max. PZD (16-bit) setpoint / actual value CU
(device)
20 / 25
20 / 25
Table 10- 27 Implicit assignment of hardware to cyclic interfaces for p8839[0] = p8839[1] = 99
Plugged hardware interface
IF1
IF2
No option, only use Control Unit onboard interface
(PROFIBUS, PROFINET or USS)
Control Unit onboard
--
CUD with CBE20 Communication Board Ethernet COMM BOARD
Control Unit onboard
PROFIBUS or Control
Unit onboard USS
Parameter p8839[0,1] is used to set the parallel operation of the hardware interfaces and the
assignment to the cyclic interfaces IF1 and IF2 for the Control Unit drive object.
The object sequence for process data exchange via IF2 depends on the object sequence
from IF1; see "List of drive objects" (p0978).
The factory setting of p8839[0.1] = 99 enables the implicit assignment (see previous table).
An alarm is generated in case of invalid or inconsistent parameterization of the assignment.