Descriptions of functions
10.7 EtherNet/IP
SINAMICS DCM DC Converter
526
Operating Instructions, 12/2018, A5E34763375A
10.7.2
Configuration of SINAMICS DCM for EtherNet/IP
10.7.2.1
Setting the IP address and activating the EtherNet/IP protocol
Requirements
●
Version with option G00/G10 (Advanced CUD)
●
CBE20
The IP configuration is performed via STARTER or through direct parameter input via the
BOP or AOP30.
Table 10- 46 Settable parameters on the drive object CU
Parameter
Note
p8941
IP address
Setting is mandatory
p8943
Subnet screen
Setting is mandatory
p8942
Default gateway
-
p8940
Name of station
In contrast to PROFINET, setting is not mandatory.
p8945 = 2
Save and activate IP
configuration
Setting must be made when the parameters are
entered directly.
In addition to direct input, the IP address can also be obtained via DHCP.
Configuration of EtherNet/IP on the drive unit
1.
For setting the IP address directly via parameters, see the previous table.
2.
Activation of EtherNet/IP
–
Set access level 3 (p0003 = 3) in the drive object CU (BOP object 1) via STARTER,
BOP or AOP30.
–
Activate the device configuration on the CU by setting p0009 = 1.
–
Activate EtherNet/IP by setting p8835=4 on the CU.
–
Complete the device configuration on the CU by setting p0009 = 0.
–
Save the parameters (copy RAM to ROM).
–
Switch the device off and on again (POWER ON).
–
After power-up, the SINAMICS DC MASTER is visible as Ethernet/IP slave in the
network.