Commissioning
8.5 Commissioning with the STARTER commissioning tool
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
315
⇒
Select the PROFIdrive telegram type.
●
1: Standard telegram 1, PZD-2/2
●
3: Standard telegram 3, PZD-5/9
●
4: Standard telegram 4, PZD-6/14
●
20: SIEMENS telegram 20, PZD-2/6
●
220: SIEMENS telegram 220, PZD-10/10
●
352: SIEMENS telegram 352, PZD-6/6
●
999: Free telegram configuration with BICO (default setting)
Note
If a standard telegram is selected, BICO interconnections are triggered which cannot be re-
parameterized. If, e.g. p0840 is to be changed again, a switchover to free telegram
configuration has to be made first.
⇒
Click Next >