Monitoring Functions
9.6 0-20 mA - 4-20 mA
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
61
Response, Delay (CiR) at Trip Level
Here you can set:
●
how SIMOCODE pro should respond if the set Trip Level is either undershot or overshot
●
the delay time.
Response
Trip level
Disabled
X
Signaling
X
Warning
-
Tripping
X
Delay
0 to 25.5 s
Preset
0.5 s
Response, Delay (CiR) at Warning Level
Here you can set:
●
how SIMOCODE pro should respond if the set Warning Level is either undershot or
overshot
●
the delay time.
Response
Warning level
Disabled
X
Signaling
X
Warning
X
Tripping
-
Delay
0 to 25.5 s
Preset
0.5 s