Logic Modules
13.7 Flickering
SIMOCODE PRO V PN FDI
124
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
13.7
Flickering
Flickering
You can use the Flickering logic modules to assign the "Flickering" function to the Operator
Panel LEDs (for example).
If an input signal is pending, the Flickering function block issues an output signal with a
frequency of 4 Hz.
The function block consists of:
●
1 plug
●
1 logic component
●
1 socket (Flickering Output).
Overall, there are 3 Flickering 1 to 3 logic modules.
Settings Flickering
Input
Activation by any signal (any sockets e.g. device inputs, signals,
status, etc.).
13.8
Limit Monitor
13.8.1
Limit Monitor
Limit Monitor
Any analog values (2 bytes/1 word) can be monitored for limit overshooting or
undershooting. The Limit Monitor issues the "limit" signal to its socket. In addition, Limit
Monitors can be "labeled" according to their function. Example: Monitoring the individual
sensor measuring circuits of the Temperature Module (Temperature 1 - 3) for
overtemperature.
The limit monitor consists of:
●
1 analog plug
●
1 logic component
●
1 socket (Event-Limit Monitor Output).
In total, 6 limit monitors (1 to 6) for the SIMOCODE pro V PN basic unit are available.