Standard Functions
12.1 Test - Reset
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
87
12.1.3
Reset
Reset
Carrying out Reset
Resetting can be carried out as follows:
●
Via the "TEST/RESET" button on the Basic Unit and on the Operator Panel (can be
deactivated) as well as via PC with the Device Integration Manager.
●
Via the "Reset Input" plug of the internal function blocks via the plugs of the internal
function blocks Reset 1, Reset 2 and Reset 3.
●
Via the menu of the Operator Panel with Display (e.g. the "commands" menu item).
Reset 1-3 - Input
Control of the Reset function block from any signal (any sockets, e.g. device inputs, control
bits from PROFINET, etc.)
Reset 1-3 - TEST/RESET button blocked
The blue TEST/RESET buttons on the Basic Unit and on the Operator Panel are intended for
acknowledging faults and carrying out device tests.
The buttons can be locked via "TEST/RESET buttons blocked". These can then be used for
other purposes. On the Operator Panel with Display, blocking is carried out via the menu
(default: unblocked).
Acknowledgement of faults
Generally, the following applies to the acknowledgement of faults:
●
Faults can be acknowledged:
–
If the cause of the fault has been eliminated.
–
If there is no "ON" control command pending.
●
A reset will not be possible if the cause of the fault has not been eliminated or if an "ON"
control command is pending. The reset will be saved depending on the type of fault.
Saving a reset is indicated by the "GEN. FAULT" LED on the Basic Unit and on the
Operator Panel. The LEDs change from flashing to continuous signal.
Automatic acknowledgement of faults
Faults are automatically acknowledged in the following cases:
●
A reset has been saved and the cause of the fault is no longer present (user has
previously acknowledged the fault).
●
Auto-reset of overload tripping or thermistor tripping if motor protection reset = Auto
(acknowledgement is automatic following expiration of the cooling down period). The
motor cannot start immediately since resetting is not possible if an ON command is
pending.