Outputs
11.7 Cyclic Send Data
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
83
Settings
Byte 0 to 1Bit 0 to bit 7Basic types 1*, 2
Controls of the bits with any signals(any
sockets, e.g. Device Inputs, Send Data, etc.).
Byte 2/3Basic types 1*, 2
Control of 1 word (2 bytes) with any analog
values (any sockets e.g. maximum current
I_max, remaining cooling time, actual value of
timers, etc.)
Byte 4/5, 6/7, 8/9Basic type 1*
Control of 3 words (6 bytes) with any analog
values (any sockets)
*) For Basic Unit SIMOCODE pro V only
Byte 0 of the signaling data is already preset. Byte 2/3 is preset with the max. current I_max!
Cyclic Services PROFINET
The Cyclic Send data are exchanged between the IO Device (SIMOCODE pro) and the IO
Controller (automation system). The IO Controller sends the Cyclic Receive data to
SIMOCODE pro in each case. In response, SIMOCODE pro returns the Cyclic Send data.
Cyclic Send Data
Description
Byte 0 to 1
Bit 0 to Bit 7
Basic types 1*, 2, 3**
Control of bits with any signals (any sockets,
e.g. device inputs, Send Data, etc.).
Byte 2/3
Basic types 1*, 2, 3**
Control of 1 word (2 bytes) with any analog
value (any sockets, e.g., maximum current
Imax, remaining cooling down period, actual
value of timers, etc.)
Byte 4/5, 6/7, 8/9
Basic type 1*
Control of 3 words (6 bytes) with any analog
values (any sockets)
Byte 10/11, 12/13, 14/15, 16/17, 18/19
Basic type 3**
Control of 5 words (10 bytes) with any analog
values (any sockets)
*) For basic unit SIMOCODE pro V only
**) For basic unit SIMOCODE pro V PN only
Byte 0 of the send data is already preset. Byte 2/3 is preset with the max. current I
max
!