Logic Modules
13.8 Limit Monitor
SIMOCODE PRO V PN FDI
126
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
13.8.2
Limit Monitor 1-6
Limit Monitor 1-6
Settings:
Input
Analog plug of the Limit Monitor to be connected with the analog value (2 bytes) which
is to be monitored, (e.g. maximum current I
max
, remaining cooling time, actual value of
Timers, etc.).
Type
Specifies if the limit value has to be monitored for overshooting or undershooting.
Activity
Determines in which motor operating state the Limit Monitor is to be evaluated:
•
on, i.e. always evaluate, independent of whether the motor is running or not
•
on+, i.e. always evaluate, independent of whether the motor is running or not;
exception: "TPF", i.e. motor feeder is in test position.
•
run, i.e. evaluate only if the motor is in the ON state and not in test position (TPF)
•
run+, i.e. evaluate only if the motor is running and the start-up procedure is
finished (i.e. the "start active" message is no longer pending) and there is no Test
Position Feedback (TPF);
Example: Cos phi Monitoring.
Limit
Monitor response value. The return value is always determined by the "Limit Monitor -
delay" parameter.
Range: 0 - 65535.
Delay
Specifies the time period for which the limit must be constantly overshot before the
"signal - limit" output is set.
Range: 0 - 25.5 s (0.5 s)
Marking
No parameters. Optional marking to designate the signal, e.g. "Limit>";
Range: Max. of 10 characters.