Inputs
10
10.1
Digital Inputs
Digital Inputs
Basic Unit - Inputs
SIMOCODE pro has a BU Inputs function block with four binary inputs with common
potential. You can connect e.g. the buttons for a Local Control Station to the Inputs. These
signals can be used for further processing in SIMOCODE pro by internally connecting the
sockets of the BU Inputs function block.
The BU Inputs function block consists of:
●
Input Terminals located on the outside of the Basic Unit, corresponding to the sockets
"BU Input 1" to "BU Input 4".
●
Sockets in SIMOCODE pro that can be connected to any plugs, e.g. to the Control
Stations function block.
●
A socket for the "TEST/RESET" button: The function of the "TEST/RESET" button is
generally dependent upon the operating status of the device.
●
Reset function for the acknowledgement of any pending faults.
●
Test function for carrying out device tests.
In addition, other functions can be assigned to the "TEST/RESET" button (e.g. operation of
the memory module and the addressing plug).
Application examples
The inputs can be used, for example, for connecting the start and stop buttons of the Local
Control Station, which can then be assigned to the Local-Control Station function block. If
assigned accordingly, the input signals can also be used to activate function blocks such as
"RESET" or "External Fault".
Basic Unit - delay time inputs
You can set a delay time for the inputs, if required.