Standard Functions
12.8 Watchdog (PLC/DCS monitoring)
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
107
Settings PLC/PCS monitoring
Bus Monitoring
•
Activated: If a bus fault occurs, the "Trip - Bus" fault
message is generated and must be acknowledged.
•
Deactivated: No fault message; however, the "Status
- Bus o.k." information can be evaluated at anytime.
PLC/PCS monitoring - Input
Control of the Watchdog function block using the
monitored signal (any sockets, e.g. control bits from
PROFINET, etc.
PLC/PCS monitoring
•
Activated: If an SPS fault occurs, the "Trip -
PLC/DCS" fault message is generated and must be
acknowledged.
•
Deactivated: No fault message; however, the "Status
- PLC/DCS in Run" information can be evaluated at
anytime.
Bus/PLC-Fault - Reset
You can select whether faults are to be acknowledged
automatically or manually.
Range: Manual/Automatic.