Monitoring Functions
9.5 Active Power
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
59
Response, Delay (CiR) at trip level
Here you can set:
●
how SIMOCODE pro should respond if the set trip level is undershot
●
the delay time.
Response
Trip level
Disabled
X
Signaling
X
Warning
-
Tripping
X
Delay
0 to 25.5 s
Preset
0.5 s
Response, Delay (CiR) at warning level
Here you can set:
●
how SIMOCODE pro should respond if the set warning level is undershot
●
the delay time.
Response
Warning level
Disabled
X
Signaling
X
Warning
X
Tripping
-
Delay
0 to 25.5 s
Preset
0.5 s