Online Settings and Displays
17.2 Command
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
143
Command
Meaning
Memory module write protection on
All contents of the memory module are write protected.
This prevents any inadvertent changes to the contents
of the memory module and any parameter changes for
the connected SIMOCODE pro V PN basic unit., pro V
3.1 and pro S.
An inadvertent change of parameters for a motor
feeder is prevented.
SIMOCODE pro signals the successful execution of
the command with the event "Memory module write-
protected"
Memory module write protection off
With this command you can cancel the write protection
of the memory module.
Initialization module write protection on
All contents of the initialization module are write
protected. This prevents any inadvertent changes to
the contents of the initialization module and any
parameter change for the connected SIMOCODE pro
V PN basic unit, pro V 3.1 and pro S.
An inadvertent change of parameters for a motor
feeder is prevented.
SIMOCODE pro signals the successful execution of
the command with the event "Initialization module
write-protected".
Initialization module write protection off
With this command you can cancel the write protection
of the initialization module.
Initialization module identification data
write protection on
(Identification & Maintenance) are write-protected. With
this command you can:
•
Prevent inadvertent changes to the PROFINET
parameters (e.g., device names) and the I&M data
for the motor feeder.
•
Continue making parameter changes in the
initialization module as well as in the SIMOCODE
pro V PN basic unit, pro V 3.1 and pro S, if the
address data and I&M data are identical to the data
already contained in the device when parameters
are downloaded.
SIMOCODE pro signals the successful execution of
the command with the event "Initialization module
identification data write-protected".
Initialization module identification data
write protection off
With this command you can cancel the write protection
of the identification data of the initialization module.