Service and maintenance
8.3 Firmware update
SIMATIC RF360R
Configuration Manual, 03/2022, C79000-G8976-C629-02
95
8.3.2
Update firmware via TIA Portal (STEP 7 Basic / Professional)
This section is intended only for S7 users.
Requirements
•
The reader is connected to the controller or PC via Industrial Ethernet or PROFINET.
•
The IP address of the reader is stored in the module parameters.
•
The reader is separated from running operation.
Note that performing the update while the application is running can slow down both the
update and command processing.
•
The required update files were stored locally.
Procedure
Proceed as follows to perform a firmware update of the reader via STEP 7 Basic / Professional
(TIA Portal):
1.
Start the TIA Portal.
2.
Open your existing project and change to the project view.
3.
Change to the network view.
4.
Right-click on the required reader and select the "Online & diagnostics" entry in the shortcut
menu.
5.
Select the entry "Functions > Firmware Update via Web Interface".
6.
Click the "Run firmware update" button.
Reaction: The WBM of the reader opens in your Web browser.
7.
Continue the firmware update as described in the section "Updating the firmware via WBM
(Page 94)".