Service and maintenance
8.2 Error messages
SIMATIC RF360R
86
Configuration Manual, 03/2022, C79000-G8976-C629-02
Flashin
g of the
reader
LED
Block (hex)
Error description
--
0xE2FE8700 There is more than one transponder in the transmission window.
--
0xE3FE0100 The file name is not allowed.
--
0xE3FE0200 The file does not exist.
--
0xE4FE0100 Warning in the event of low power supply
The power supply is very close to the low limit.
--
0xE4FE0200 Hardware fault
28
0xE4FE0300 Connection problem with the reader
Error in the connection to the reader; the reader is not answering.
Possible causes / action to be taken:
•
The PROFINET or power supply cable is wired incorrectly or there is a cable break.
•
The 24 V supply voltage is not connected or is not turned on or has failed briefly.
•
The hardware is defective.
•
RF300: Antenna is not identified
Possible causes: Antenna is not connected or antenna cable is defective.
•
Perform an "init_run" once the error has been corrected.
19
0xE4FE0400 The buffer on the communications module or reader is not adequate to store the command
temporarily.
--
0xE4FE0500 The buffer on the communications module or reader is not adequate to store the data
temporarily.
--
0xE4FE0600 The command is not permitted in this status or is not supported.
Possible causes:
•
The "INIT" command has been concatenated.
•
Command repetition was started without "Presence mode".
--
0xE4FE0700 Startup message from reader/communications module
The reader or communications module was off and has not yet received a "Reset_Reader"
("WRITE-CONFIG") command.
Possible causes / action to be taken:
•
Execute the "INIT" command.
•
The same physical address in the "IID_HW_CONNECT" parameter is being used more than
once. Check your "IID_HW_CONNECT" parameter assignments.
•
Check the connection to the reader.
•
The device has not yet been restarted after the change to the transmission speed.
--
0xE4FE8100 The specified tag field of the transponder is unknown.
--
0xE4FE8A00 General error
--
0xE4FE8B00 No or bad configuration data/parameters were transferred.
Possible causes:
•
You are accessing a read point that is not configured.