Service and maintenance
8.2 Error messages
SIMATIC RF360R
Configuration Manual, 03/2022, C79000-G8976-C629-02
91
8.2.3
XML error messages
A list of the possible XML error codes can be found in the "XML programming for SIMATIC
Ident (
https://support.industry.siemens.com/cs/ww/en/view/109781631
)" manual.
8.2.4
OPC UA error messages
The following table lists the OPC UA-specific error codes.
Table 8- 5
OPC UA error messages of the communication module / reader
AutoId
status
OPC UA
status
AutoId
text
Error description
1
good
MISC_ERROR_
TOTAL
General error
1
good
MISC_ERROR_
TOTAL
•
Firmware error
Possible cause: The firmware update was not run
completely.
•
Internal communications error of the communications
module/reader
–
Connector contact problem on the communications
module / reader
–
Hardware of the communications module/reader has a
defect; →
Send in communications module/reader for
repair
–
Start "INIT" after correcting the error
•
Internal monitoring error of the communications
module/reader
–
Program execution error on the communications module
/ reader
–
Turn the power supply of the communications
module/reader off and on again
–
Start "INIT" after correcting the error
1
good
MISC_ERROR_
TOTAL
The "Inventory" command failed.
1
good
MISC_ERROR_
TOTAL
Enabling write protection on the transponder has failed.
1
good
MISC_ERROR_
TOTAL
The "Kill" command failed.
3
good
PERMISSON_
ERROR
The transponder is read/write-protected.
4
good
PASSWORD_
ERROR
The transponder password is incorrect. Access is denied.
5
Bad
Invalid
Argument /
good
REGION_NOT_
FOUND_ERROR
All commands:
A parameter of an OPC UA command has an invalid value.
"ReadTag"/"WriteTag" command:
The addressed memory area is not available in the current
transponder.