WARNING
Ignitions of gas-air mixtures
• When using the RF380T transponder, check that the temperature class is kept to in
conjunction with the requirements of the area of application.
If the temperature ranges are exceeded during use of the transponder, gas-air mixtures may
be ignited.
• The maximum transmit power of the transmitter used to operate the transponder must not
exceed 2 W.
If the transmit power id not kept to, gas-air mixtures may ignite.
7.8.6.2
Installation and operating conditions for the hazardous area
a) Use of the equipment in the vicinity of processes generating high charges is not allowed.
b) The equipment must be mechanically protected when installed.
7.8.7
Technical specifications
Table 7-22
RF380T technical specifications
6GT2800-5DA00
Product type designation
SIMATIC RF380T
Memory
Memory organization
in bytes
Memory configuration
• UID
• 4 bytes EEPROM
• User memory
• 32 KB FRAM
• OTP memory
• 20 bytes EEPROM
Read cycles (at < 40 ℃)
> 10
10
Write cycles (at < 40 ℃)
> 10
10
Data retention time (at < 40 ℃)
> 10 years
Write/read distance (S
g
)
Dependent on the reader used, see section "Field
data of RF300 transponders (Page 50)"
Mechanical specifications
Enclosure
• Material
• PPS
• Color
• Anthracite
Recommended distance to metal
≥ 0 mm
RF300 transponder
7.8 SIMATIC RF380T
SIMATIC RF300
System Manual, 02/2021, C79000-G8976-C345-09
295