![Siemens SIMATIC RF300 System Manual Download Page 50](http://html.mh-extra.com/html/siemens/simatic-rf300/simatic-rf300_system-manual_374416050.webp)
If the entire voltage range at the reader of 20 VDC to 30 VDC and/or the entire temperature range
of transponders and readers is used, the field data is subject to further tolerances.
Note
Transmission gaps
If the minimum operating distance (S
a
) is not observed, a transmission gap can occur in the
center of the field. Communication with the transponder is not possible in the transmission gap,
see section "Impact of secondary fields (Page 44)".
Note
Possible reader-transponder combinations
The tables of the following section show the possible reader-transponder combinations.
Note
Deviations for antennas with plug-in antenna cable
When using antennas with a plug-in 60 cm antenna cable, note that deviations of 10 - 20% can
occur for the field data.
4.2.1
Field data of RF300 transponders
The limit distances (S
g
) and operating distances (S
a
) along with the length of the transmission
window for each reader-transponder combination are listed in the tables below.
In dynamic mode, make sure that rectangular transponders cross the antenna field in the
longitudinal direction.
Table 4-2
Field data RF310R reader
Length of the transmission
window (L)
Operating distance (S
a
)
Limit distance (S
g
)
RF320T
30
1...23
26
RF330T
30
2...18
21
RF340T
40
2...36
41
RF350T
45
2...47
53
RF360T
45
2...60
68
RF370T
70
2...45
60
All values are in mm
The values relate to the RF310R reader as of version "D".
Planning the RF300 system
4.2 Field data for transponders, readers and antennas
SIMATIC RF300
50
System Manual, 02/2021, C79000-G8976-C345-09