be called with various attributes or modes (subcommands) for which corresponding data
structures (UDTs) are defined.
Table 10-2
In RF300 mode
Command
Attributes
(mode)
Meaning
Reader-Status
(SLG-STATUS)
0x81 (01)
Hardware and firmware configuration, parameterization status
0x86 (06)
Communication error counter, current command status
Tag-Status
(MDS-STATUS)
0x81 (01)
Serial number of the transponder (UID), memory configura‐
tion.
EEPROM write-protection status
0x82 (02)
Serial number of the transponder (UID), HF field strength value,
communication error counter, presence counter (duration)
0x83 (03)
Serial number of the transponder (UID), transponder type iden‐
tified in the antenna field (number = tag type, see Reset - "ftim"
parameter), memory configuration, write protection status
(OTP), size and number of blocks in the user memory
Overview of the diagnostic functions
Table 10-3
In ISO mode: ISO 15693, ISO 18000-03 or ISO 14443
Command
Attributes
Meaning
Reader-Status
(SLG-STATUS)
0x81 (01)
Hardware and firmware configuration, parameterization status
0x86 (06)
Communication error counter, current command status
Tag-Status
(MDS-STATUS)
0x83 (03)
Serial number of the transponder (UID), transponder type iden‐
tified in the antenna field (number = tag type, see Reset - "ftim"
parameter), memory configuration, write protection status
(OTP), size and number of blocks in the user memory
10.2.2
Reader diagnostics with "reader status" (SLG-STATUS)
With this command you can query the status and diagnostics data of the reader.
Note
Scope of the described UDTs
Note that below only the variables are listed that are relevant for the RF300 system. You will find
the full UDTs in the manual "Ident Profile and Ident Blocks".
System diagnostics
10.2 Diagnostics functions - STEP 7
SIMATIC RF300
System Manual, 02/2021, C79000-G8976-C345-09
427