Procedure
1. Open the "General" tab and the "I\Os" tab in the "Object Properties" dialog box for each
listed block.
– Enter the parameters for all blocks according to the table below.
Note
For the "STRUCT" data type (e.g., "SimOn.Value"):
● Select the "Open structure" command from the shortcut menu.
The "Structure - <I/O name>" dialog box opens.
● Double click "Value".
Block
Block
name in
the project
I/O
Meaning
Value
Pcs7DiIn
FbkRun
SimOn.Value *
Switch simulation active
1
Feature.Bit29
Enables a substitute value
1
SimPV_In.Value * Simulation value PV
0
MotL
Motor
Monitor
Deactivate monitoring
0
ModLiOp.Value *
Automatic/manual mode selection 0
AutModOp
Disable automatic mode
0
Feature.Bit4
Set switch or button mode (switch
mode)
1
* Invisible in CFC, see "Note"
– Do not set a check mark for "Create block icons" in the "General" tab for the following
blocks: Interloc, Permit, Protect.
2. Click "OK" for each block.
Your settings are applied.
3. Close the chart.
6.6.14
Interconnection of blocks in the CFC charts
Interconnection of Blocks
Now, you can interconnect the inputs and outputs in the charts. To interconnect the blocks:
1. Click on the graphic user interface of the CFC editor.
2. Click on the output of a block and on the input that you want to interconnect.
3. After clicking on the input, the interconnection is displayed as a line. The CFC Editor
automatically draws lines in the best position. The position of the lines has no impact on
the function of the interconnection.
Creating CFCs
6.6 Working with the CFC Editor
PCS 7 SMART Getting Started - Part 1 (V9.0 with APL)
92
Getting Started, 12/2017, A5E42181435-AA