43
Fire brigade periphery module FCI2001-D1 [DE]
Indicators
246
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
5
6
X2
LA ausgel
UE ausgel
7
8
0V
+24V
1
2
3
4
5
6
X3
UE ab
BMZ rueckst
7
8
Ak Sign ab
Bf St ab
1
2
3
4
Bf St ab
Ak Sign ab
BMZ rueckst
UE ab
UE pruefen
Reserve
Reserve
+
-
1
2
3
4
5
6
7
8
9
10
11
12
13
1
The connection details correspond to the FBF Type Wiesmeier FBF0770
2 Only switch possible
43.4
Indicators
LED
Color
Function
Condition
Meaning
H201
Yellow
fire department operating panel
Off
Normal operation
On
Fault: Overload protection active (short-circuit)
H301
Yellow
Remote transmission and
transmission device
Off
Normal operation
On
Fault: Overload protection active (short-circuit)
H302
Yellow
Fire department key depot:
Unlocking
Off
Normal operation
On
Fault: Overload protection active (short-circuit)
H303
Yellow
Fire department key depot: Heater Off
Normal operation
On
Fault: Overload protection active (short-circuit)
H401
Yellow
Identification lamp
Off
Normal operation
On
Fault: Overload protection active (short-circuit)
H402
Yellow
Local alarm
Off
Normal operation
On
Fault: Overload protection active (short-circuit)