27
Line card (MS9i) FCL2003-A1
Technical data
158
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
27.6
Technical data
Supply input
Voltage
DC 20…30 V (Vsys)
Current
Max. 0.75 A
Detector line
Output voltage
Max. DC 24.9 V
Number of integrated line cards
1
Output current (all outputs together)
Max. 0.5 A
Plug-type connection for card cage
Number of devices with 2 loops
Max. 100
Number of devices with 1 loop and 1 stub
Max. 82
Number of devices with 2 stubs
Max. 64
Connectable lines
2 loops or
2 stubs or
1 loop and 1 stub
Protocol
MS9i
Cable types
All types (recommended: twisted); for
detailed specifications see document
008843
Monitored for
Ground fault
Short-circuit
Open line
Design
Short-circuit-proof
Overvoltage protection (on card cage)
Supply output for MS9i devices
200 mA
Mechanical data
Dimensions (L x W x H)
160 x 120 x 15 mm
Weight
117 g
Ambient conditions
Operating temperature
Min. -5 °C max. +50 °C
Storage temperature
Air humidity
Min. -20 max. +60
Max. 93 % rel. air humidity (EN 6006-2)
Standards and approvals
VDS
QA Standards
CE conformity mark
LPCP