Network module (SAFEDLINK) FN2001-A1
15
Indicators
99
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
B2
A2
B1
A1
1
2
3
4
FCM 200x
FN2001
X3
X13
FCnet
FCnet
Wiring of 1 network module
B2
A2
B1
A1
B2
A2
B1
A1
1
2
3
4
1
2
3
4
FCM 200x
FN2001
FN2001
X3
X3
X13
X12
FCnet
FCnet
Wiring of 2 network modules
The main module must always be plugged in slot X13 of the operating unit
FCM20xx.
When two network modules are used, the degraded mode module must be
plugged in slot X12 of the FCM20xx operating unit.
15.4
Indicators
LED Color
Function
Condition Meaning
H1
Green
Condition of the
network module
(SAFEDLINK)
Off
Network module (SAFEDLINK) is defective
On
Normal condition (H2 and H3 are off)
Flashes
Normal condition for degraded mode module (H2 and H3 are off)
H2
Yellow Status of line 1
(A1, B1)
Off
Normal condition
(communication on line 1 is OK)
On
Fault on line 1;
(no communication on line 1)
H3
Yellow Condition of line
2
(A2, B2)
Off
Normal condition
(communication on line 2 is OK)
On
Fault on line 2;
(no communication on line 2)