EVAC-NL operating unit FTO2007-N1
Pin assignments
252
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
The operating add-on FCM2008-N1 (option) is installed in the bottom part of the
fire control panel and is connected via the peripheral data bus.
Peripheryboard
FTO2007
PMI & Mainboard
FCM20xx
FTO2007
RS485
FCA2002
FTI2002
FC20xx
Vsys
RS485
Vext.
FTI2002
X1
X1
X1
X1
X4
X4
FCM2008-N1
1
2
X400
X402
Wiring of the remote EVAC 20-zone display via the RS485 interface
1
Any housing (e.g. ECO housing)
2
Operating add-on FCM2008-N1 with 2 x EVAC-NL FTO2007-N1 (option)
The two EVAC-NL operating units FTO2007-NL must be linked to each other for
synchronization via the peripheral data bus (X400 – X402). If the LED indicators on
the two components do not flash in synch, this indicates that they are not
connected to one another.