Network module (SAFEDLINK) FN2001-A1
Technical data
100
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
15.5
Technical data
Supply input
Voltage
DC 21…30 V
Operating current
Max. 45 mA
System bus
Voltage
DC 5 V
Current
Max. 100 mA
Impedance
120
Cable type
Shielded and unshielded cables
Example:
Uninet 30044PFRNC(KAT6)
R&M fseenet KAT5e F/UTP 4P
Communication cable J-
2T(St)TSTIIIBD
CCM 2C1.5T1/1254(MICC)
Fire detection cable
JY(St)Y2x2x0.8mm red
Protocol
SAFEDNET (UDP/IP)
Data rate in operation mode:
'Standard'
312 kbit/s
'Low'
96 kbit/s
Distance between 2 network modules
Max. 1000 m
Electrical isolation between the FCnet and
the station
1 kV
Monitored for:
Short-circuit
Open line
Ground fault
Communication error
Connections
System bus:
Design
Screw terminals 0.2…2.5 mm
2
(0.8 mm
2
recommended)
Admissible cable cross-section
0.8 mm
2
Operating unit
Plug-type connection
Mechanical data
Dimensions (W x H x D)
50 x 20 x 70 mm
Weight
20 g