RT interface FCI2006-C1 [CH]
48
Indicators
297
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
RT interface
Cable tree
4 loop periphery board
2 loops periphery board
12
Fault
White
1 (+ 2)
X7-5 FAU_COM
X7-5 FAU_COM
13
K1
Black
2
--
--
--
--
14
K1
Brown
2 + 3
--
--
--
--
15
K2
Green
2
--
--
--
--
16
K2
--
3
--
--
--
--
17
K3
Gray/pink
2
--
--
--
--
18
K3
--
3
--
--
--
--
19
K4
--
--
--
--
--
--
20
K4
--
3
--
--
--
--
Cable no.:
Cable 1 to periphery board, control cable VDE LI-CY 0.34 mm
2
, 14-pin, length
560 mm, included in cable set
Cable 2 to RT device, control cable 14-pin VDE LI-CY 0.34 mm
2
, length
700 mm, included in cable set
Cable 3 = loop made from wire jumpers 3 x 0.22 mm
2
x 40 mm
48.4
Indicators
LED
Color
Function
Condition
Meaning
H1-1
Red
Relay 1
Off
Quiescent condition, relay inactive
On
Relay activated
H1-2
Red
Relay 2
Off
Quiescent condition, relay inactive
On
Relay activated
H2-1
Red
Relay 3
Off
Quiescent condition, relay inactive
On
Relay activated
H2-2
Red
Relay 4
Off
Quiescent condition, relay inactive
On
Relay activated
H3
Yellow
Test
Off
Quiescent condition
On
Test mode active (key S1 pressed)
48.5
Adjustment elements
The switching contacts of the relays K1…K4 and the 'Alarm' and 'Fault' test
contacts must be configured as 'normally open' (NO) or 'normally closed' (NC). The
application-specific configuration is made by inserting a wire jumper (0
resistance) between the corresponding solder pins.
The following figure shows a configuration example using relay K1.
NC
NO
X3
Y3
K1
13
14