I/O card (horn/monitored) FCI2009-A1
29
Indicators
169
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
29.4
Indicators
Standard LED indicators
LED
Color
Function
Condition
Meaning
H301
Yellow
Signal of module
bus driver
Off
Normal condition
Flashes slowly Degraded mode
1 x flashing
(every 2 s)
Update begins
2 x flashing
(every 2 s)
Update running
3 x flashing
(every 2 s)
Update failed
Flashes rapidly Incorrect test, update needed
OUT1
Yellow
Status of
monitored
output 1
Off
Normal operation
Slow
Fault:
Connection interrupted or
short-circuited
(Priority 2)
Fast
Fault:
Overload fuse active
(Priority 1)
Pulsating
- Calibration invalid
- Calibration running
(maximum 25 seconds)
(Priority 3)
On
Output activated
(Priority 4)
OUT2…7 In accordance with OUT1 to output 2...7
MSP
Yellow Status
Line driver
Off
Normal operation
Slow
Line driver in degraded mode
(Priority 2)
Fast
General fault (Priority 1)
Pulsating
On
29.5
Adjustment elements
Button
Meaning
Function
CALIB
S501
Calibration
Starts the calibration of the
monitored outputs