Periphery board (2 loops) FCI2002-A1
7
Technical data
61
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
Monitored output
Fault
Designation
'VSYS_O'; 'FAU_OUT'
Design
Open drain
Failsafe
Activated in degraded mode
Output voltage
DC 21…28.6 V
Output current
Max. 300 mA (protected with 1 AT)
Guaranteed output current
(monitored for short circuit and open line)
15 mA with U
out min
= 16 V
Monitored for
(if output inactive)
Short-circuit
Open line
Nominal monitoring resistance
1.6 … 2.3 k
Min. tolerance
+/–
Changeover contacts
RT alarm
Designation
’AL_NO’; ’AL_COM’; ’AL_NC’
Design
Relay output
Break or make contact
Activated in degraded mode
Switching voltage
Max. DC 60 V
Switching current
Max. 400 mA
Monitored output
Alarm
Designation
''; 'AL_OUT-'
Design
Relay reversed polarity
Activated in degraded mode
Output voltage
DC 21…28.6 V
Output current
Max. 1 A (protected with 1 AT)
Guaranteed output current
(monitored for short circuit and open line)
20 mA with U
out min
= 16 V
Monitored for (if output inactive)
Short-circuit
Open line
Nominal monitoring resistance with tolerance 2.3…5.5 k
+/–
Monitored sounder (horn)
output
Designation
''; 'SOUND1-'
Design
Relay reversed polarity
Activated in degraded mode
Output voltage
DC 21…28.6 V
1
Output current
Max. 1 A (protected with 1 AT)
Guaranteed output current
(monitored for short circuit and open line)
20 mA with U
out min
= 16 V
Monitored for (if output inactive)
Short-circuit
Open line
Nominal monitoring resistance
with tolerance
2.3…5.8 k
+/–