Fire brigade periphery module FCI2001-D1 [DE]
43
Technical data
247
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
43.5
Technical data
Fire department control panel
(FBF)
Supply voltage
24 V
Supply current
Type <50 mA, max. 1A (current limited)
Design of the inputs and outputs
Active low
Short-circuit-proof
Line resistance per wire
Max. 10
Remote transmission /
transmission device
Supply voltage
24 V
Supply current
Typ. <30 mA, max. 1A (current limited)
Output (RT/RD alarm):
Voltage/current (if active)
24 V; 12 … 120 mA; max. 1 A
Design
Active high
Short-circuit-proof
Current limited
In quiescent condition monitored for
Short-circuit (incl. gradual)
Open line (incl. gradual)
Load resistance
200 … 2 k
Line resistance per wire
Max. 10
Input (RT/RD confirmation):
Design
Active low
Short-circuit-proof
Line resistance per wire
Max. 10
Releasing element (FSE)
Input FSE:
Design
Short-circuit-proof
Termination resistor for quiescent condition
3.3 k
Termination resistor for alarm
3.3 k parallel 680
Monitored for
Short-circuit
Open line
Line resistance per wire
Max. 10