Floor repeater terminal FT2010
Technical data
226
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
39.5
Technical data
Supply
Optional
Via external supply
Via FDnet detector line
External supply
Designation
'AC+', 'AC–'
Voltage
AC 15…18 V
DC 20…30 V
Power consumption
10 … 50 mA
Detector line
Designation
'LINE+', 'LINE–'
Voltage
DC 12…32 V
Power consumption
Without external supply
4…40 mA
With external supply
Max. 5 mA
Maximum current connection factor
Without external supply
160
With external supply
20
Quiescent current connection factor
Without external supply
20
With external supply
20
Address connection factor
1
Separator connector factor
1
Protocol
FDnet
Functional data
Display
6 lines of 40 characters each
Acoustic signaling
Tone interval can be configured with
SintesoWorks
Connections
Detector line and external supply
Design
Screw terminals
Cable cross-section
0.8 … 1.5 mm
2
Ambient conditions
Operating temperature
-8...+42 °C
Storage temperature
-20…+60 °C
Protection category
IP30
Max. application height
4000 m above sea level
Mechanical data
Dimensions (W x H)
283 x 207 mm
Depth of FT2010-A1
79 mm
Depth of FT2010-C1
45 mm
Weight of FT2010-A1
800 g
Weight of FT2010-C1
1100 g
Standards
Safety
EN 60950
QA Standards
Siemens Standard SN 36350
ISO 9001
ISO 14001
CE conformity mark
Yes