26
Line card (collective) FCL2002-A1
Pin assignments
152
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
26.3
Pin assignments
26.3.1
Connection terminals of line card (collective) in card cage
The line card (collective) FCL2002-A1 determines the PIN assignment of the four
connectors in the card cage.
External connections on the card cage as an example the module bus card 1 on
connectors X11 and X12
4
3
6
5
8
7
2
1
4
3
6
5
8
7
2
1
X11
X12
The external connections of module bus card 2 are on plugs X21 and X22
The external connections of module bus card 3 are on plugs X31 and X32
The external connections of module bus card 4 are on plugs X41 and X42
The external connections of module bus card 5 are on plugs X51 and X52
Connector Pin
Signal
Connection
Stub
X11
1
IO_1
Stub 1
2
IO_2
Stub _1-
3
IO_3
Stub _2+
Stub 2
4
IO_4
Stub _2-
X12
1
IO_5
Stub _3+
Stub 3
2
IO_6
Stub _3-
3
IO_7
Stub _4+
Stub 4
4
IO_8
Stub _4-
X11
5
IO_9
Stub _5+
Stub 5
6
IO_10
Stub _5-
7
IO_11
Stub _6+
Stub 6
8
IO_12
Stub _6-
X12
5
IO_13
Stub _7+
Stub 7
6
IO_14
Stub _7-
7
IO_15
Stub _8+
Stub 8
8
IO_16
Stub _8-
Admissible cable cross-section: 0.2…1.5 mm²