RT interface FCI2005-N1 [NL]
Technical data
292
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
47.6
Technical data
Supply input
Designation
'20 V-30 V VSYS+'
Voltage
Min. DC 17 V…max. DC 30 V
Quiescent current
Typically 0 mA
Quiescent current (all relays switched)
Max. 240 mA
Relays 1 … 12
Designation
'REL1' … 'REL12'
Design
Relay reversed polarity
Operating current/relay
Max. 12 mA
DC switching voltage
Max. DC 30 V
DC switching current
Max. 2 A
AC switching voltage
Max. AC 125 V
AC switching current
Max. 0.5 A
Relays 13 + 14
Designation
'REL13', 'REL14'
Design
Relay reversed polarity
Operating current/relay
Max. 30 mA
DC switching voltage
Max. DC 30 V
DC switching current
Max. 5 A
AC switching voltage
Max. AC 250 V
AC switching current
Max. 5 A
LEDs
Status indication relay
Lights up when relay is switched
Connection terminals
All connectors:
X1 … X6
Design
Screw clamps, grid 3.81 mm
Admissible cable cross-section
0.14…1.5 mm
2
rigid/flexible
X7 + X8
Design
Screw clamps, grid 5 mm
Admissible cable cross-section
0.2…2.5 mm
2
rigid/flexible
Mechanical data
Dimensions (L x W x H)
190 x 150 x 36 mm
Weight
240 g