Sounder module FCA2005-A1
31
Pin assignments
183
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
1
2
X3
S4 out-
S4 out+
3
4
S3 out-
S3 out+
+
-
-
+
3 k
3 k
The terminating resistor of 3 k also has to be connected even when the output is
not in use.
31.3.3
X2 sounder 1 and 2 outputs
Pin
Designation
Description
1
S2 out+
Sounder output 2 (+)
2
S2 out-
Sounder output 2 (-)
3
S1 out+
Sounder output 1 (+)
4
S1 out-
Sounder output 1 (-)
Admissible cable cross-section: 0.08…1.5 mm²
1
2
X2
S2 out-
S2 out+
3
4
S1 out-
S1 out+
+
-
-
+
3 k
3 k
The terminating resistor of 3 k also has to be connected even when the output is
not in use.