Repeater (SAFEDLINK) FN2002-A1
18
Pin assignments
113
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
18.3
Pin assignments
18.3.1
Connector X3
Pin
Designation
Description
1
A1
Line 1 (+)
2
B1
Line 1 (-)
3
S
Shielding
4
D
Shielding
5
E
Ground connection
6
S
Shielding
7
A2
Line 2 (+)
8
B2
Line 2 (-)
B2
A2
B1
A1
1
2
3
4
FCM200x
FN2001
X3
X13
FCnet
-
+
B2
A2
S
E
D
S
B1
A1
1
4
1
8
X3
FN2002
X2
-
+
+Usys
-Usys
B2
A2
B1
A1
1
2
3
4
FCM200x
FN2001
X3
X13
FC20xx
FC20xx
FCnet
Repeater FN2002, cabling
In the FCnet, line 1 must always be wired to line 2 or line 2 must be wired to line 1,
respectively.
18.3.2
Plug X2
Pin
Designation
Description
1
+Usys
Supply input DC +24 V
2
-Usys
Supply input 0 V
3
+Usys
Supply output DC +24 V
4
-Usys
Supply output 0 V
"Input" and "Output" are connected in parallel on the printed circuit board and can
be switched.