Operating unit with PMI & mainboard FCM2027
11
Indicators
85
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
Element
Des.
Function
Position
1
Shield plate
2
Key switch (optional)
Plug connections
X3
Connection for periphery board or fire terminal board (supply and data signals)
X5
Ethernet connection
X11
Slot for connection module (card cage) FCA2006-A1
X12
Slot for network module (SAFEDLINK) FN2001-A1; degraded mode module
X13
Slot for network module (SAFEDLINK) FN2001-A1; master module
X14
SER_OPT1, slot for series module (RS232 module FCA2001-A1 or RS485 module
FCA2002-A1)
1
X15
Reserved
X19
SER_OPT2, slot for series module (RS232 module FCA2001-A1 or for RS485
module FCA2002-A1)
1
X400
Connection for peripheral data bus
Indicators
H37…H61
H842
LED indicators
H841
Buzzer
Switches, buttons
S32
Reset key
S33
Switch for ground fault monitoring of the Ethernet connection
S37
Support for license key
S38
Switch for ground fault monitoring system supply
1
The serial modules can be loaded in any way. Two identical modules for each
PMI & mainboard can also be loaded.
11.3
Indicators
LED
Color
Function
Condition
Meaning
H37
Yellow
Diagnosis 1
Off
Normal operation
On
Ground fault present
H38
Yellow
Diagnosis 2
Not used
H39
Yellow
Diagnosis 3
Not used
H50
Yellow
'MSP fail' (processor periphery)
Off
Normal operation
On
Processor in degraded mode; replace
component or contact hotline
H51
Red
'PD ready', installation ready to switch
off
Off
Installation in operation
On
Installation may be disconnected from the
mains
H52
Yellow
'PPC fail' (CPU module)
Off
Normal operation
On
Processor in degraded mode; replace
component or contact hotline