I/O card (programmable) FCI2008-A1
28
Adjustment elements
163
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
LED
Color
Function Condition
Description
Direction
H112
Green IO_12 Off
High input (default) INPUT (default)
On
Low input
OUTPUT
Status and error displays
LED Color
Function
Conditio
n
Description
H113 Green IO_FAULT_1 Off
n.o. (normal operation)
On
I/O fault, I/O 1…4 (over temp. over current)
H114 Green IO_FAULT_2 Off
n.o. (normal operation)
On
I/O fault, I/O 5 … 8 (over temp. over current)
H115 Green IO_FAULT_3 Off
n.o. (normal operation)
On
I/O fault, I/O 9 … 12 (over temp. over current)
H116 Green IO_DIR
Off
Status indicator (button S501)
On
Direction indicator (button S501)
H301 Yellow Signal from
HCS12
Off
Active
On
Inactive
H518 Yellow Signal block Off
Inactive
On
Active
H601 Orange SI_DEF_24V_1 Off
n.o. (normal operation)
On
Fuse fault (R662)
H602 Orange SI_DEF_24V_2 Off
n.o. (normal operation)
On
Fuse fault (R663)
Degraded mode indicator
LED
Color Function
Conditio
n
Description
H117 Green Failsafe UART Off
Passive (normal operation)
Flashing
(every
2 s)
Failsafe active
28.5
Adjustment elements
Button
Meaning
Function
S301
Reset for module bus driver (if
fitted)
Resets module bus
S401
Reset for line driver (if fitted)
Resets line driver
S501
STATUS/DIRECTION switchover
(see also H116)
Status/direction indicator
switchover