34
CPU card (FC2080) FCC2004-A1
Adjustment elements
200
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
34.5
Adjustment elements
The only setting element for the user is the S8 button next to the LED matrix
display. The LED matrix display changes through the following list with a brief push
of a button for <0.5 seconds.
Display Function
Description
R
Reset
Initiate restart/booting
L
1
Access Level 3 System works at access level 3 after PIN has been entered
F
1
Factory reset
Restore to factory setting and restart/boot
U
Firmware
Update
Firmware of the main CPU is updated
S
Switch over'
Transfer of control to the second CPU card
D
Debug mode
Test mode for developers
1
These functions are displayed only on the active CPU.
The displayed function is executed at the push of a button for >1.5 seconds.
If the button is not actuated for 5 seconds, then the LED matrix display in the
standard display is switched on.
34.6
Technical data
Supply input
Voltage
DC 20…30 V
Quiescent current at 24 V with
SAFEDLINK module
140 mA
Maximum current at 24 V with
SAFEDLINK module
180 mA
Dual operation possible with CPU card
(FC2080)
FCC2004-A1
Display
LED matrix display 5 x 7 LED
LED diameter
17.8 x 12.7 mm
2 mm
Interfaces
1 x plug for serial modules
Card cage (CPU)
2 x Ethernet connection RJ45
10/100 Mbit/s
Mechanical data
Dimensions (W x H x D)
35.2 x 189 x 139.1 mm
Weight (without FN2010-A1)
206 g
Weight (with FN2010-A1)
226 g