Chapter 4) 7SR23 DAD Data Communications
©2013 Siemens Protection Devices Limited
Chapter 4 Page 13 of 54
2.1.6 Optional Rear EN100 Ethernet Module (COM3)
The optional ethernet interface is primarily provided for support of IEC 61850 protocol. Support for IEC 60870-5-
103 is also provided over this interface to allow connection with Reydisp Evolution and Reydisp Manager software
for interrogation, editing and download of relay settings and other data. Ordering options are available with two
RJ45 electrical connectors or with two duplex LC fibre optic connectors.
Setting name Range
Default
Setting Notes
LAN Protocol
OFF, IEC60870-5-103
IEC60870-5-103
If this setting is set to Off, access to relay data using Reydisp Evolution and Reydisp Manager software via the
Ethernet interface is not available.
Connections to the optional EN100 ethernet module are made on the rear underside of the relay.
Connections are made to either RJ45 sockets (electrical) or Duplex LC (fibre optic) connectors.
LED yellow
LED green
LED yellow
LED green
Ch 1
Ch 2
Ethernet – EN100-E
EN100 Module – RJ45 Interface
Ethernet – EN100-O
Ch 1
Ch 2
EN100 Module – Duplex-LC Interface
Green LED (Physical Link)
Off – No link
On – Link present
Yellow LED (Activity)
Off – No traffic
On/flashing - Traffic
Figure 2-8
EN100 Ethernet Module
Summary of Contents for 7SR23 DAD
Page 1: ...Answers for energy 7SR23 DAD High Impedance Protection Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...7SR23 DAD Contents 2013 Siemens Protection Devices Limited ...
Page 60: ...Chapter 3 7SR23 DAD Performance Specification 2013 Siemens Protection Devices Limited ...
Page 225: ......