Chapter 3) 7SR23 DAD Performance Specification
©2013 Siemens Protection Devices Limited
Chapter 3 Page 19 of 20
3.2 74TCS Trip Circuit Supervision
3.2.1 Reference
Parameter
Value
t
d
Delay setting
0, 0.02…60 s
3.2.2 Operate and Reset Time
Attribute
Value
t
basic
Element basic operate time
30ms 10ms
t
op
Operate time following delay
t
basic
+
t
d
, 1 % or 20ms
Repeatability
1 % or 10ms
-10 °C to +55 °C
5 %
Variation
f
nom
± 5%
5 %