Chapter 3) 7SR23 DAD Performance Specification
©2013 Siemens Protection Devices Limited
Chapter 3 Page 15 of 20
Section 2: Protection Functions
2.1
50G Instantaneous Measured Earth Fault
2.1.1 Reference
Parameter
Value
Is
Setting
0.01…2.0 x
In
t
d
Delay setting
0, 0.005…1.0, 1.01…5,5.1…60s
2.1.2 Operate and Reset Level
Attribute
Value
I
op
Operate level
100 %
Is
, 5 % or 1%
In
Reset level
95 %
I
op
or 1%
In
Repeatability
1 %
Transient overreach
(X/R 100)
-5 %
-10 °C to +55 °C
5 %
Variation
f
nom
± 5%
5 %
2.1.3 Operate and Reset Time
Attribute
Value
2 x
Is
, 22ms 5ms 50Hz, 2 x
Is
, 18ms 5ms 60Hz
3 x
Is
, 1 cycle, 5ms
t
basic
Element basic operate time
5 xI
s
, < 1 cycle
t
op
Operate time following delay
t
basic
+
t
d
, 1 % or 10ms
Repeatability
1 % or 10ms
Overshoot time
< 40 ms
Disengaging time
< 50 ms