Chapter 3) 7SR23 DAD Performance Specification
©2013 Siemens Protection Devices Limited
Chapter 3 Page 12 of 20
1.4.2.5
High Frequency Disturbance (Immunity) / 1MHz Burst High Frequency Disturbance
IEC 60255-22-1
Type
Level Variation
Case, Aux Power & I/O Common (longitudinal) mode
2.5 kV
Case, Aux Power & I/O Series (transverse) mode
1.0 kV
10 %
RS485 Metallic Comms
1.0 kV No data loss
1.4.2.6
Electrostatic Discharge (Immunity)
IEC 60255-22-2 Class IV, IEC 61000-4-2
Type
Level Variation
Contact discharge
8.0 kV
5 %
1.4.2.7
Radiated Immunity / Radiated Electromagnetic Field Disturbance
IEC 60255-22-3 Class III,
Type
Level Variation
80 MHz to 1000 MHz
10 V/m
5 %
1.4.2.8
Electrical Fast Transient / Burst Immunity
IEC 60255-22-4 Class A (2002),
Type
Level Variation
Case, Aux Power & I/O
4kV
10 %
RS485 Metallic Comms
2.0 kV No data loss
1.4.2.9
Surge Immunity
IEC 60255-22-5, IEC 61000-4-5
Type
Level Variation
Analog Inputs Line to Earth
4.0 kV
Case, Aux Power & I/O Line to Earth
2.0 kV
10 %
RS485 Comms port Line to Earth
1.0 kV No data loss
Analog Inputs Line to Line
1.0 kV
Case, Aux Power & I/O Line to Line
1.0 kV*
10 %
* Note 45ms pick up delay applied to binary inputs
1.4.2.10
Conducted Radio Frequency Interference (Immunity)
IEC 60255-22-6
Type
Level Variation
0.15 to 80 MHz
10 V
5 %