Chapter 4) 7SR23 DAD Data Communications
©2013 Siemens Protection Devices Limited
Chapter 4 Page 35 of 54
OBJECT
REQUEST
(Library will parse)
RESPONSE
(Library will respond with)
Object
Number
Variation
Number
Description
Function Codes
(dec)
Qualifier Codes
(hex)
Function Codes
(dec)
Qualifier
Codes (hex)
1
(read)
22
(assign class)
00, 01
(start-stop)
06
(no range, or all)
07, 08
(limited qty
17, 27, 28
(index
)
20
0
Binary Input – Any
Variation
7
(freeze)
8
(freeze noack)
9
(freeze clear)
10
(frz. cl. noack)
00, 01
(start-stop)
06
(no range, or all)
07, 08
(limite
d qty)
20
1
32-Bit Binary Counter
(with Flag)
1
(read)
00, 01
(start-stop)
06
(no range, or all)
07, 08
(limited qty)
17, 27, 28
(index)
129
(response)
00, 01
(start-stop)
17, 28
(index –
see note 2)
20
2
16-Bit Binary Counter
(with Flag)
1
(read)
00, 01
(start-stop)
06
(no range, or all)
07, 08
(limited qty)
17, 27, 28
(index)
129
(response)
00, 01
(start-stop)
17, 28
(index –
see note 2)
20
3
32-Bit Delta Counter
(with Flag)
20
4
16-Bit Delta Counter
(with Flag)
20
5
(default –
see note
1)
32-Bit Binary Counter
without Flag
1
(read)
00, 01
(start-stop)
06
(no range, or all)
07, 08
(limited qty)
17, 27, 28
(index)
129
(response)
00, 01
(start-stop)
17, 28
(index –
see note 2)
20
6
16-Bit Binary Counter
without Flag
1
(read)
00, 01
(start-stop)
06
(no range, or all)
07, 08
(limited qty)
17, 27, 28
(index)
129
(response)
00, 01
(start-stop)
17, 28
(index –
see note 2)
20
7
32-Bit Delta Counter
without Flag
20
8
16-Bit Delta Counter
without Flag
21
0
Frozen Counter –
Any Variation
1
(read)
22
(assign class)
00, 01
(start-stop)
06
(no range, or all)
07, 08
(limited qty)
17, 27, 28
(index)
21
1
32-Bit Frozen
Counter (with Flag)
1
(read)
00, 01
(start-stop)
06
(no range, or all)
07, 08
(limited qty)
17, 27, 28
(index)
129
(response)
00, 01
(start-stop)
17, 28
(index –
see note 2)
21
2
16-Bit Frozen
Counter (with Flag)
1
(read)
00, 01
(start-stop)
06
(no range, or all)
07, 08
(limited qty)
17, 27, 28
(index)
129
(response)
00, 01
(start-stop)
17, 28
(index –
see note 2)
Summary of Contents for 7SR23 DAD