3.4 Protection: Mode Selection
3.4.1 ‘3 Pole Diff’ + REF’ Operation
The relay is configured for ‘3 Pole Diff +REF’ operation using the
SYSTEM CONFIG > Relay Config > 3 Pole Diff
+ REF
setting. Protection elements are automatically enabled as shown in Figure 3-5.
When configured in this way the relay uses the 87/50-n and the REF-1 elements. These elements operate
independently of each other. Independent outputs are available.
When 87/50-n Trip Check Logic is Enabled outputs are available when any two phases operate (i.e. 87/50-n
phase-phase check).
For detailed information on the differential and restricted earth fault functions refer to sections 3.1and 3.3.
Blk
Pickup
Operate
87REF-1 Setting
Enable
IG
87REF-1 Pickup
87REF-1
87REF-1 Delay
74
TCS
x12
87
REF
1
3
1
87/
50-1
87/
50-2
CT50
7SR23
DAD
1
General Pickup
87/50-n Delay
&
87/50-n Setting
Enable
Inhibit 87/50-n
IA
IB
IC
Blk
Pickup
Operate
Blk
Pickup
Operate
Blk
Pickup
Operate
CT50C
&
Inhibit 87/50C-n
1
CT50B
&
Inhibit 87/50B-n
1
CT50A
&
Inhibit 87/50A-n
1
87/50-n
Disabled
Enabled
User Inhibit 87/50-n
87/50-n CT50
Inhibit
Disabled
Enabled
87/50AB-n
87/50B-n
87/50A-n
87/50C-n
Zone Switch Out
&
87/50BC-n
87/50CA-n
&
&
87/50-n Trip
Check Logic
Enabled
Disabled
Notes
For details of data communications points refer to Technical Manual, Chapter 4 (Data Communications).
For details of user logic inputs and outputs refer to the relevant Reydisp Manager template.
87REF-1
Disabled
Enabled
&
Inhibit 87REF-1
User Inhibit 87REF-1
1
87/50-n
Figure 3-5 Logic Diagram: ‘3 Pole Diff + REF’ Protection