Chapter 1) 7SR23 DAD Description Of Operation
©2013 Siemens Protection Devices Limited
Chapter 1 Page 21 of 36
3.4.2 ‘3 Pole Diff + EF’ Operation
The relay can be used to provide both 3 phase differential and earth fault protections using the
SYSTEM CONFIG
> Relay Config > 3 Pole Diff + EF
setting.
When configured in this way the relay uses the 87/50-n and the 50G-n elements. These elements operate
independently of each other, an output may be given only when both are operated – see Figure 3-6 below.
When 87/50-n Trip Check Logic is Enabled outputs are available when any two phases operate (i.e. 87/50-n
phase-phase check) or when an 87/50 element operates coincidentally with the 50G element (phase-earth
check).
For detailed information on differential and earth fault functions refer to sections 3.1and 3.2.
Notes
For details of data communications points refer to Technical Manual, Chapter 4 (Data Communications).
For details of user logic inputs and outputs refer to the relevant Reydisp Manager template.
74
TCS
x12
50G
(x2)
3
1
87/
50-1
87/
50-2
CT50
7SR23
DAD
1
General Pickup
87/50-n Delay
&
87/50-n Setting
Enable
Inhibit 87/50-n
IA
IB
IC
Blk
Pickup
Operate
Blk
Pickup
Operate
Blk
Pickup
Operate
CT50C
&
Inhibit 87/50C-n
1
CT50B
&
Inhibit 87/50B-n
1
CT50A
&
Inhibit 87/50A-n
1
87/50-n
Disabled
Enabled
User Inhibit 87/50-n
87/50-n CT50
Inhibit
Disabled
Enabled
87/50AB-n
87/50B-n
87/50A-n
87/50C-n
Zone Switch Out
&
87/50BC-n
87/50CA-n
&
&
87/50AG-n
&
87/50BG-n
&
87/50CG-n
&
En
Pickup
Operate
50G-n
Disabled
Enabled
&
50G-n Setting
Enable
Inhibit 50G-n
IG
General Pickup
50G-n
50G-n Delay
User Inhibit 50G-n
50G-n
Measurement
Fundamental
RMS
EF IN (Control)
87/50-n Trip
Check Logic
Disabled
Enabled
1
87/50-n
Figure 3-6 Logic Diagram: ‘3 Pole Diff + EF’ Protection